Design power transformers pdf




















Further length of the winding will increase resulting higher resistance so more cu loss. Consider permeability of iron as infinity that is MMF is needed only for leakage flux path in the window. The leakage flux lines are parallel to the axis of the core. Consider an elementary cylinder of leakage flux lines of thickness dx at a distance x as shown in following figure.

Total weight is equal to weight of above all parts. Motor Rating By chris by. Download PDF. If the high-voltage winding has an external neutral, this is brought out to a neutral bushing marked H0. The phase leads of the low-voltage windings are con- nected to low-voltage bushings labeled X1, X2, and X3.

If the low-voltage winding has an external neutral, this is brought out to a neutral bushing marked X0. If the high-voltage bushings are connected to a three-phase system with a phase rotation H1-H2-H3, the phase rotation of the low-voltage bushings is X1-X2-X3. The placement of the bushings in a three-phase transformer is also stan- dardized. When bushings are mounted on the top of the transformer lid, the high-voltage bushings are arranged H0, H1, H2, and H3 from left to right in the upper half of the lid, as seen from above the transformer.

The low-voltage bushings are arranged X0, X1, X2, and X3 from left to right in the lower half of the lid, as seen from above the transformer. If side-mounted low-voltage bushings are used, they are arranged X0, X1, X2, and X3 from left to right facing the transformer from the low-voltage side. If side-mounted high-voltage bushings are used, they are arranged H3, H2, H1 and H0 from left to right facing the transformer from the high-voltage side.

The proper connections are shown in Figure 2. The H1 bushings are always on the upper left of the lid, per the standard arrangement. The low- voltage bushings are labeled according to whether the transformer is additive or subtractive. When the low-voltage windings are connected phase-to-neutral, the X1 bushings are normally connected to the phase wires and the X2 bush- ings are connected to the neutral.

Chakan, Jr. ANSI Std. IEEE Std. The conditions expressed by the ideal transformer laws are approached, but never realized in physical transformers. Transformed voltages and currents are always less than the val- ues predicted by the turns ratio because of losses. This chapter explains the origins of transformer losses and develops the concept of equivalent circuits of real transformers.

Figure 3. In Figure 3. Since the total ampere-turns in the primary are approximately equal to the total ampere-turns in the secondary, the wind- ings are simply drawn with the same number of turns with the same current in each turn. The spaces between the two windings and between the windings and the core are shown greatly exaggerated. The magnetizing current is assumed to be negligible compared to the load currents.

The situation in a real transformer is somewhat different than described above. For the time being, suppose the load connected to the trans- former secondary is purely inductive. This would naturally increase the voltage induced across the primary. This can be accomplished only if the number of lines within the core decreases to two lines pointing upward.

The opposite situation exists for the secondary winding. But as shown in the preceding paragraph, the number of lines in the core must also decrease by two lines to balance the voltage across the primary winding. This suggests that some sort of inherent restriction or impedance limits the short-circuit currents in the transformer.

The vector relationships are shown in Figure 3. The relationship between load current and secondary voltage is equiva- lent to placing a physical impedance in series with the output of an ideal FIGURE 3. Leakage reactance limits short-circuit currents, and is therefore useful, but it also reduces the secondary voltage under load regu- lation and consumes reactive power. Varying the winding dimensions and the spacing between the windings can control the amount of leakage reactance.

It was determined that the resistance of the winding is proportional to the con- ductor length divided by the conductor cross-sectional area. These additional losses affect the transformer design to some extent.

These currents generate local I 2 R losses even if the conductor itself is not carrying any net electrical current. Therefore, the square of eddy currents and the eddy-current losses are both proportional to the square of the load current.

These eddy losses are externally manifested by a component that increases the effective resistance of the conductors, even if the eddy losses occur in metallic parts that are electrically isolated from the conductors. Let this eddy-loss component of the conductor resistance be de- noted R e. The concentration of current toward the edge of a conductor is called the skin effect, reducing the area of the conductor that actually carries current and increasing the effective resistance of the conductor.

The skin effect is more pronounced for large-diameter conductors. Let the skin-effect component of the conductor resistance be denoted R s. The conductor losses are equivalent to placing a lumped resistance in series with the terminals of an ideal transformer.

Conductor losses are com- monly referred to as load losses, because they result only from load currents. Load losses are sometimes referred to as copper losses; however, this is some- what of a misnomer. Load losses limit the KVA capacity of a transformer because the heat generated by these losses increase temperatures. Therefore, it is highly desir- able to reduce the load losses as much as possible by reducing the AC resis- tance of the conductor. Shortening the conductor length can only be achieved to a point, and increasing the conductor cross-sectional area has the unfortunate effect of increasing both the eddy-current losses and the skin- effect losses.

These losses can be reduced by special conductor designs. Subdividing the conductors into strands that are insulated from each other to break up the eddy current paths can reduce eddy-current and skin- effect losses.

By subdividing one large-area conductor into a number of small-area conductors, the skin effect is substantially reduced as well. Transposition allows the current to divide equally among the strands to optimize the use of the entire cross section area of the conductor.

The transposition of a seven-strand cable is illustrated in Figure 3. After seven complete transpositions, all the strands return to their original positions. All of the above factors, except the frequency, are under the control of the transformer designer. Core losses are sometimes referred to as iron losses and are commonly referred to as no- load losses, because core losses do not require load currents.

This obviously involves increasing the numbers of turns in both the primary and secondary windings in order to maintain the same transformer turns ratio. As we saw earlier, the disadvantage of adding more turns is that this increases the length of conductor and increases the conductor resistance. More cross- sectional area is required in order to keep the resistance constant.

Doubling the number of turns requires about four times the volume of copper. These additional localized core losses must be factored into the calculation of the total core losses.

Burrs are imperfections that form electrical bridges between the laminations and create paths for eddy currents and increased losses. Some- times the eddy currents near a burr can be large enough to cause localized overheating that can actually cause core damage.

Core losses are approximately proportional to the square of the excita- tion voltage E applied to the transformer. Therefore, placing an equivalent linear conductance G m across the transformer terminals can approximate trans- former core losses. Determine the voltage difference between adjacent lam- inations along the perimeter of the core. There are laminations in the core: 24 in. Therefore, the voltage difference between each pair of laminations is calculated below.

Refer to Figure 3. Solving for R, 0. It is a good idea to design the core with some electri- cal conductivity between the laminations to prevent static charges from build- ing up between the laminations. Static charges in the core are allowed to bleed off to ground through an electrical connection at a single point, called the core ground.

It was shown earlier that the magnetizing current is not really sinusoidal, but contains many odd harmonics in addition to the fundamental frequency. In a two-winding transformer, this is equivalent to placing a reactance X m, called the magnetizing reactance, in parallel with the transformer terminals.

The peak value of the magnetizing current is determined from the B-H curve of the core, which we have seen is very nonlinear. It is generally desirable to maximize X m in order to minimize the mag- netizing current. All ripples or waves must be eliminated by compressing the core laminations together tightly.

The leakage reactance is expressed as an inductive reactance in series with the secondary winding, but it is more correctly shown as split between the primary winding X p and the secondary winding X s. Simi- larly, the load losses are expressed as resistance R p , in series with the primary winding, and resistance R s , in series with the secondary winding. An ideal transformer is connected behind the series impedances. The magnetizing re- actance X m is approximated by a constant value, and the core losses are repre- sented by a conductance G m.

These last two elements are shunted in parallel with the ideal transformer. The complete equivalent circuit of the transformer is shown in Figure 3. This equivalent circuit can model all of the electrical properties of a two-winding transformer.

It must be mentioned here, however, that the equivalent circuit shown in Figure 3. A slightly different equivalent circuit must used in zero phase sequence networks. The meanings of these terms will be explained in Section 3. Since typical values of magnetizing reactance are several orders of mag- nitude greater than typical values of leakage reactance, and since no-load losses are usually much smaller than load losses when the transformer is car- rying rated load, the elements G m and X m can be neglected in most calculations.

If voltages and currents are expressed in per unit instead of using actual system voltages and currents, the ideal transformer in the model will have a turns ratio and can thus be eliminated from the equivalent circuit. Since R p , R s , X p , and X s are now all directly in series with each other, the resistance elements can be combined into a single resistance R and the reactance elements can be combined into a single reactance X. The equivalent circuits of transformers modeled in zero phase sequence networks are different from those in positive and negative phase sequence networks.

The zero-sequence equivalent circuit depends on the type of wind- ing connections used; these equivalent circuits will be developed a little later in this chapter. Before continuing with transformer equivalent circuits, it is necessary at this point to digress with a brief tutorial on symmetrical components. Therefore, a brief tutorial on symmetrical components is presented here that will provide an understanding of positive, negative, and zero phase sequence voltages and currents and how the concept of symmetrical components is applied to transformers.

When three-phase circuits are balanced, calculations of voltages and cur- rents are simple and straightforward. In these instances, the actual circuit and its positive phase sequence network are one and the same thing. The positive phase sequence network is nothing more than a network where the phase rota- tion is positive normally A-B-C and the phases are balanced; i.

Although the ideal set of balanced conditions may exist approximately under normal conditions, this is rarely the case for design-limiting conditions such as system faults. When voltages, currents, or impedances are unbalanced, the solutions become much more complex, especially when there is mutual induction between various parts of the circuit, as in the case of three-legged core form transformers with the three phases coupled magnetically through the core.

There have been several methods for attacking three-phase circuit prob- lems for unbalanced conditions, but the most successful method in use today is called symmetrical components. In this method, an unbalanced circuit is represented by a combination of three balanced circuits, called sequence net- works. The positive phase sequence network has already been described above.

In the negative phase sequence network, the voltages and currents of all three phases are balanced but the phase rotation is opposite to the positive phase sequence; i. It is usually assumed that there are no negative or zero phase sequence voltage sources. In the zero-phase sequence network, the voltages and currents of all three phases are identical and are all in phase with each other; i.

Since the phase currents are in phase, these add together at the neutral. Therefore, zero phase sequence networks always involve neutral or ground currents. Zero-sequence currents exist only if there are physical ground current paths in the circuit. A set of unbalanced phase currents, I a , I b , and I c , may be transformed into a set of symmetrical components I 0 , I 1 , and I 2 , where I 0 is the zero phase sequence current, I 1 is the positive phase sequence current, and I 2 is the nega- tive phase sequence current.

There is also a set of sequence currents that is referenced to B phase, and a set of sequence currents referenced to C phase as well. The symmetrical component method does not require explicitly solving all three sets of sequence currents, because these sets of sequence currents are identical to each other except that they are shifted in phase.

There- fore, it is implicitly understood that the sequence currents I 0 , I 1 , and I 2 are always referenced to A phase. So far, it may seem that all this has accomplished is additional work; however, the additional work usually makes calculations involving unbalanced circuits much easier than dealing with phase quantities alone. We will see a direct application of this method at the end of this chapter.

The following steps summarize the technique of symmetrical compo- nents: 1. Transform the sequence voltages and currents at the point of the fault calculated in step 2 back into phase voltages and currents using Eqs.

The corresponding sequence network con- nections for these unbalanced conditions are shown in Figure 3. We shall soon see that in zero sequence networks, the transformer equivalent circuits can be very different depending on the connections and type of core construction. This section will show how to develop the zero phase sequence equivalent circuits for the vari- ous types of transformers. The basic equivalent circuit consists of series impedance elements be- tween the primary and secondary windings, and a shunt impedance.

The shunt impedance is approximately equal to the open-circuit impedance Z oc measured at the primary windings with the secondary windings open-circuited, or mea- sured at the secondary windings with the primary windings open-circuited. If per-unit values are used, Z oc is approximately the same whether it is measured at the primary or secondary winding.

The basic zero phase sequence trans- former equivalent circuit is shown in Figure 3. As we will soon see, the value of the shunt impedance is radically differ- ent for different types of core construction and winding connections.

In most cases G m is practically zero and the magnitude of X m is much greater than the magnitudes of R p and X p.

The arrows in Figure 3. A similar result applies to the open-circuit impedance of a three-phase, three-legged core form transformer with the winding Y connected. A three-phase, three-legged core form transformer is shown in Figure 3. Zero phase sequence voltages excite both of these transformers.

This same effect exists for three-phase shell form transformers when excited by zero-sequence voltages. This could easily drive the core into saturation. The exact value of Z oc is uncertain at best in these cases. The series transformer impedance for zero phase sequence networks also depends on how the transformer is connected. The diagrams in Figure 3. As previously discussed, the mag- netizing impedance Z M varies depending on the core construction. This situation can occur when a Grd.

Y- Grd. Y transformer is energized by a three-phase source with an open phase. Example 3. It is desired that the types of core con- struction of these transformers be determined prior to putting them into ser- vice. Using a single-phase VAC 60 Hz source and an ammeter, devise a test to determine which types of core construction these transformers have. The neutral bushing H0 was connected to the grounded neutral leg of the VAC source.

The low-voltage bushings were open-circuited. Based on the measured currents, all the transformers have zero-sequence open-circuit currents less than mA with the exception of transformer 4, which had a zero-sequence open-circuit current of 1. The measured open-circuit current is 1. It is easily seen in this example how the zero- sequence equivalent circuits are affected by the core design. This impedance has a very low power factor, consisting almost entirely of leakage reactance with only a small resistance.

As discussed earlier, the transformer design engineer can control the leakage reactance by varying the spacing be- tween the windings. While leakage reactance can be considered a transformer loss because it consumes reactive power, some leakage reactance is necessary to limit fault currents.

On the other hand, excessive leakage reactance can cause problems with regulation. This requires the primary voltage to be greater than the rated primary voltage at full load. Let E p equal the primary voltage and let E s equal the secondary voltage when the transformer is fully loaded.

Using per-unit values instead of primary and secondary voltage values, the per-unit secondary voltage will equal E p with the load removed. For a near-unity power factor, the regulation is much smaller than the regulation for an inductive load with a small lagging power factor.

The three-phase fault is a balanced fault, so the positive-sequence equiv- alent circuit applies. The turns ratios of all of the transformers must be nearly equal. The phase angle displacements of all of the transformers must be identical. The primaries of the two transformers are connected to a 66 kV transmission line through a single air break switch. This switch is designed to interrupt magnetizing current only, which is less than 1 A.

The transformers were being removed from service and the second- ary loads had been removed. A switchman then started to open the air break switch, expecting to see a small arc as the magnetizing current was interrupted. Something was obviously wrong. Because the turns ratios were unequal, a circulating current was set up even without any secondary load.

The open- circuit secondary voltage difference, assuming 66 kV at the transformer pri- maries, is calculated below. But since the turns ratios are not equal, I c does not get transformed into equal and opposite currents at the primaries. The resulting current exceeded the interrupting rating of the switch, causing it to fail. The conditions described in this example are diagramed in Figure 3. If single-phase transformers are connected in a Y-Y bank with an iso- lated neutral, then the magnetizing impedances should also be equal on an ohmic basis.

Otherwise, the transformer having the largest magnetizing imped- ance will have a highest percentage of exciting voltage, increasing the core losses of that transformer and possibly driving its core into saturation.

The general case where all three transform- ers have different impedances is derived below. Note: In general, these ratios are complex numbers because the impedances are com- plex numbers. The currents i a , i b , and i c are multiplied by 1. The graph in Figure 3. The temperature rise of the winding is caused by all of the transformer losses that were previously discussed in this chapter. There- fore, the winding temperature is a function of load losses and no-load losses. Thermal capability is the KVA load applied to the output of a transformer that causes the hottest area in the windings, called the winding hot spot, to reach some limiting temperature.

The hot-spot tempera- ture determines the rate of loss of life of the transformer as a whole, which is a cumulative effect. Therefore, the hot-spot temperature limit is usually based on a loss-of-life criterion.

The standard method for calculating the ther- mal capability of oil-insulated transformers will be covered fully at the end of this chapter. When one purchase order is used to procure a number of identical transformers from the same manufacturer, some testing is performed on each transformer while certain other tests are performed only on one representative unit in that pur- chase order.

There is a recommended format of a transformer test report [1]. Some transformer manufacturers follow the recommended format exactly while others prefer to use their own format, but the information contained in the test reports is standard throughout the industry. A sample test report is shown in Figure 3. It was based on an actual factory test report for an order of four transformers used in a generating station. In the upper portion of the test report is the general design information, such as the cooling class, number of phases, frequency rating, rated temperature rise, voltage ratings of the windings, and the KVA rating.

The transformers shown in Figure 3. This means that heat is transferred from the core and coils to the insulating oil, which is forced through the transformer by oil pumps. The heat is then transferred from the insulating oil to the ambient air through a set of radiators which have air forced through them by fans.

The voltage rating of the HV winding is Grd. The full winding rating from phase to ground is , V. Additional HV winding taps are available at ,, ,, ,, and , V. The full winding rating is the same as the phase-to-phase system voltage, 23, V. The methods used in performing factory tests will be covered in more detail in Chapter 8.

Since typical magnetizing current power factors are extremely small, core loss measurements require carefully calibrated test equipment. At the bottom of the test report are the results of a heat run test. The heat run test applies a load equal to the nameplate KVA rating of the transformer at full voltage using an inductive load.

Using an inductive load reduces the en- ergy use during this test. It is an expensive and time-consuming test, so it is usually only performed on one of the transformers on a purchase order. In the case of this sample test report in Figure 3. Note from the test report, however, that the HV winding only attained a Therefore, the as-built transformer has a 5.

It is this increased loading, and not the nameplate rating, that is the true thermal capability of that transformer. The average winding temperatures are not di- rectly measured in this test. Instead, the winding temperatures are inferred from conductor resistance measurements taken immediately after the test is shut down.

The last two entries on the test report are the hot spot temperature rise of the HV and LV windings. These values are not actually measured by any test, but are calculated based on the average winding temperature and the oil temperature. There is only about a 6. This is fairly typical of transformers in the FOA cooling class.

Since cooling oil is forced through the windings by pumps, the oil velocity is quite high. For transformers without oil pumps, such as the self-cooled OA class or forced-air cooled only FA class , the oil velocities are much slower and there is a much greater temperature gradient between the hot spot temperature and the average winding temperature. This method can be applied to trans- formers of any MVA size.

A generally accepted value for m is 0. Most engineers consider the winding time constant to be very short, and a value of zero is used by some. Although the IEEE method seems rather complicated, it is straightforward enough with the use of a desktop computer. The IEEE standard includes a computer program in Basic code that performs the temperature calculations.

Satisfactory results can be obtained with just a few step changes over the course of 24 h, but better accuracy will be achieved if the load cycle is broken into 1 h intervals. The relation of insulation aging to time and temperature fol- lows the well-known Arrhenius chemical reaction rate model.

The adaptation used in the IEEE standard [3] has the following form. Normal life for most transformers is considered to be around 30 to 40 years. The constants A and B depend on the types of material used to insulate the windings. To calculate the equivalent aging of the transformer F EQA with a varying hot-spot temperature such as occurs for a cycling load or a seasonal ambient temperature, F AA is integrated over time and the integral is divided by the total time to obtain the average.

The per unit life and F AA are plotted vs. It should be stressed that most transformer failures are random events that occur for various reasons besides insulation loss of life. Therefore, the formula for per unit life cannot be used as a predictive model to determine when a given transformer will ultimately fail. However, it is indeed certain that overloading a transformer will shorten its life, so it is a good practice from FIGURE 3. From the test report, it is clear that the HV winding has the higher tem- perature and is the limiting winding.

To calculate the thermal capability pre- cisely, a trial-and-error approach is used where the MVA loading is varied and the temperatures are calculated until the desired per unit life is achieved. The Y-connected generator is grounded through a resis- tance. A bolted phase-to-ground fault occurs at one of the HV terminals of the transformer.

The three-phase diagram of the actual circuit is shown in Figure 3. In this example, we will use the generator ratings for the common MVA base. Let us assume that the series winding impedance of the transformer bank is purely reactive all leakage reactance. Convert the The positive phase sequence, negative phase sequence and zero phase sequence networks are connected in series for a phase-to-ground fault on A phase, as shown in FIGURE 3.

Calculating the HV sequence currents, 1. The two-phase load current is 1 per unit in each secondary winding. Calculate the positive, negative, and zero phase se- quence currents in the three-phase circuit in per unit. The T connection uses a transformer between A phase and neutral to supply one-half of the two-phase load and a 1.

The ammeter reads 0. Calculate the open-circuit zero phase sequence impedance of this transformer, in per unit of the transformer rating. Calculate the per-unit load in each transformer on its own base.

Using the method described in Section 3. Additionally, the current in transformer C must be divided by 1. What are the positive-, negative-, and zero-sequence voltages at the generator? The primary of the transformer is modeled as three ideal transformers with series impedances of j0. The voltages across the windings are E a , E b , and E c. Y bank, so at the generator these voltages are: Zero sequence 0 Positive sequence 1. National Electrical Manufacturers Association.

Transformers, Regulators and Re- actors. TR , Part 7, pp. It is used quite extensively in bulk power transmission systems because of its ability to multiply the effective KVA ca- pacity of a transformer.

Autotransformers are also used on radial distribution feeder circuits as voltage regulators. The connection is shown in Figure 4. In two-winding transformers, the primary voltage is associated with the primary winding, the secondary voltage is associated with the secondary winding, and the primary voltage is normally considered to be greater than the secondary voltage. The output terminals operate at a higher voltage than the input terminals. The other possible connection for an autotransformer is shown in Figure 4.

The autotransformer shown in Figure 4. The key feature of an autotransformer is that the KVA throughput of the transformer, i. The output terminals operate at a lower voltage than the input terminals.

The volts per turn in the common winding equal the volts per turn in the series winding. The common winding voltage divided by the series winding voltage is equal to the number of turns in the com- mon winding divided by the number of turns in the series winding.

The sum of the ampere-turns of the common winding plus the am- pere-turns of the series winding equal the magnetizing ampere- turns. The magnetizing ampere-turn are practically zero, so the mag- nitude of the ampere-turns in the common winding is approximately equal to magnitude of the ampere-turns in the series winding. The series winding current divided by the common winding current is equal to the number of turns in the common winding divided by the number of turns in the series winding.

This is illustrated in the following example. Example 4. The current low-voltage input current is A. Refer to Figure 4. This is a consider- able multiplication of KVA capacity. The capacity multiplication factor F c is a function of the ratio of the output voltage to the input voltage r. F c for a boosting autotransformer is always greater than 1, and it is always greater than F c for a bucking autotransformer for a given value of r.

The chart shown in Figure 4. The heavy curve is for a boosting autotransformer and the lighter curve is for a bucking autotransformer. A boosting autotransformer begins to lose its advantage over a two-winding transformer as the voltage ratio increases. Consider a two-winding transformer having a turns ratio n connected as a boosting autotransformer.

The transformer impedance, which is mainly leak- age reactance, is split between the common winding and the series winding as Z c and Z s , respectively. The magnetizing impedance is neglected. To deter- mine the impedance of the autotransformer, the secondary low-voltage termi- nals are short-circuited and a voltage source E p is applied to the primary high- voltage terminals, as shown in Figure 4. This is obtained by dividing both sides of Eq.

For a large ratio n this impedance is much smaller than the series impedance seen at the primary side. In general, the series impedance of a small two-winding transformer is greater than the series impedance of a large two-winding transformer if the two impedances expressed as percent of the winding KVA bases are equal. However, when a small transformer is connected as an autotransformer the series impedance seen at the transformer terminals can be substantially smaller than the impedance of a much larger equivalent two-winding transformer.

Recall from Eq. Recall- ing the capacity multiplication factor of a boosting autotransformer in Eq. In Section 4. What is the impedance of the autotransformer ex- pressed as a percent of the KVA capacity of the autotransformer? In Example 4. This ratio is calculated below. In other words, the This example clearly illustrates the tremendous savings in economy that can be realized by using the autotransformer connection. The transformer is connected as a single-phase boosting auto- transformer in a single-phase radial distribution circuit.

The input to the autotransformer is V single phase. Converting the impedance to the autotransformer KVA capacity base, r 1. For this rea- son, this autotransformer connection is seldom, if ever, used.

The Grd. Y connection using autotransformers is indistinguishable from a Grd. Y connection using two-winding transformers. This is the most common connection using autotransformers. The phase shift is a function of the ratio of the primary to secondary voltages and it can be calculated from the vector diagram, such as the example shown in Figure 4. The situation is very different when a short circuit is applied to an auto- transformer, as can be seen from the circuit diagram shown in Figure 4.

This almost guarantees that the core will go into saturation, with two immediate results. First, the admittance of the magnetizing branch of the transformer can no longer be ignored, and the admittance of the magnetizing branch is very nonlinear with the core in saturation; therefore, short-circuit current calculations are some- what uncertain for autotransformers.

Second, with the core in saturation, the transformer essentially becomes an air-core transformer, further limiting the ability to calculate impedances. Fortunately, this also limits the magnitude of the induced voltage across the common winding. These solutions have everything you need to create your model from start to finish. Customers say that RALE is a powerful solution that helps businesses built high-quality transformers and indicators.

Being one of the words best solutions means you can never go wrong with RALE. DadMatrac Transformer design is suitable for designers who want to develop step up, step down, tapped primary, and tapped secondary transformers. You can even create your custom core library with DadMatrac. Soft Bit Online gives you the power to modify core and conductor insulation, connection groups and flux density.

By optimizing your design, you will get desired costing, average possible losses, performance, and more. Prolific Transformer Design Software is easy to use solution. It features a simple user interface, fast loading speed and it is the best tool for those who are looking for a simple tool to work with.

Being able to design your model on platforms other than the popular and commonly used Windows Operating System does make it possible for you to design the best object for your project irrespective of your type and version of your Operating System.

Here is a list of the additional software solutions that you will find useful.